-40%

Ground Earth Resistance Tester Explosion Proof Type 0.01 to 1200Ω Alarm Function

$ 173.44

Availability: 100 in stock
  • Data Storage:: 99 sets
  • Protection Level: Double insulation
  • Structural Feature: Clamp CT
  • Clamp Size: 65mm×32mm
  • External Magnetic Field: <40A/m
  • External Electrical Field: <1V/m
  • Country/Region of Manufacture: China
  • Ground Resistance Resolution: 0.001Ω
  • Single Measurement Time: 0.5 second
  • Alarm Threshold Setting:: 1-199Ω
  • Restocking Fee: No
  • Return shipping will be paid by: Buyer
  • MPN: 2020369841
  • Item must be returned within: 30 Days
  • Brand: VTSYIQI
  • Accuracy: Resistance: ±1%±0.01Ω; Current:±2.5%±1mA
  • Refund will be given as: Money back or replacement (buyer's choice)
  • Features: Clamp
  • All returns accepted: Returns Accepted
  • Condition: New
  • Ground Resistance Range: 0.010Ω~1200Ω

    Description

    Clamp Earth Resistance Tester Explosion Proof Type 0.01 to 1200Ω Alarm Function
    Instruction:
    ETCR2000B+ Explosion Proof Type Clamp Earth Resistance Tester is our company's technology research and development team on technical quality of the pursuit of excellence, through continuous innovation to improve, upgrade with the old product. Its performance is mainly reflected in:
    Breakthrough in self-test the boot a long time to waiting, start immediately into the test.
    Breakthrough relay self-test mode, using the most advanced processing algorithms and digital integration technology.
    Breakthrough the old product to heavy issues, more in line with characteristics of hand-held devices.
    New design, panel operation with 6 buttons, better performance.
    Increase sound and light alarm function, with "beep-beep-beep” alarm sound.
    Increase the interference signal recognition indicator function, with "beep-beep-beep” indicator.
    Measurement range: 0.01Ω-1200Ω
    Stored data 99 Units. Lower power consumption, Maximum operating current less than 50mA.
    ETCR2000B+ Explosion Proof Type Clamp Earth Resistance Tester is widely used in the grounding resistance measurement of the power, telecommunications, meteorology, oilfield, construction and the industrial and electrical equipment. In the measurement of a grounding system with loop, does not require breaking down the grounding down lead, and no need the auxiliary electrode. It is safe, fast and simple in use. The tester can measure ground faults which cannot be measured by traditional methods. It can be used in applications where traditional methods cannot be measured, because theETCR2000B+ Explosion Proof Type Clamp Earth Resistance Tester measures the combined value of grounding body resistance and grounding lead resistance.
    ETCR2000B + type clamp meter has passed the certification of explosion-proof and met GB3836-2000 explosive gas environment with electrical equipment. The explosion-proof marks is Exia

    BT3Ga. Explosion-proof qualified number:CE18.2380.It can be applied to the corresponding inflammable and explosive environment.
    Product Main Function
    1. Measurement of earth resistance,loop resistance
    2. Resistance Measure Range: 0.010Ω~1200Ω
    3. Data Storage: 99 sets
    4. Alarm Threshold Setting

    1-199Ω
    5. Alarm Function: audible and visible alarm
    6. Ex-mark :Exia

    BT3Ga
    7. Explosion-proof Certification :CE18.2380
    Specification:
    Function
    Test of earth resistance and loop resistance
    Power Supply
    6VDC 4 PCS of LR6 lkaline batteries
    Clamp Size
    65mm×32mm
    LCD Size
    4 Digits LCD display, Screen: 47mm×28.5mm
    Range
    Resistance: 0.010Ω~1200Ω
    Resolution
    Resistance: 0.001Ω
    Accuracy
    Resistance: ±1%±0.01Ω; Current:±2.5%±1mA
    Data Storage
    99 sets
    Data Upload Function
    RS232 Interface (Optional)
    Auto Power-off
    Automatically power off after 5 minutes without any operation
    Power Consumption
    ≤50mA

    continuously working for 30 hours
    Working Environment
    -20

    ~55
    ℃;
    20%rh~80%rh
    Store Environment
    -20

    ~60
    ℃;
    below 90%rh
    EX-Mark
    Ex ia

    BT3Ga
    Explosion-proof Certification
    CE18.2380
    Alarm Threshold Setting Range
    Resistance

    1~199Ω
    Audible and Visible Alarm
    “Beep-beep-beep” alarm sound, alarm symbol flashing, press AL key to turn on/off and setting
    Interference Signal Recognition
    “Beep-beep-beep” indicator, NOISE symbol blinking
    Protection Level
    Double insulation
    Structural Feature
    Clamp CT
    Shift
    Automatic shift
    External Magnetic Field

    40A/m
    External Electrical Field

    1V/m
    Single Measurement Time
    0.5 second
    Resistance Measurement Frequency

    1KHz
    Measured Current Frequency
    50/60Hz Automatic
    Low Battery Voltage Indication
    When the battery voltage is lower than 5.3V, the low battery voltage symbol is displayed
    Storage Full Indication
    Storage data full of 99 sets,flashed display "MEM" symbol
    Over Range Indication
    Over range indication “OLΩ”, “L0.01” or “OL A”
    Tester Weight
    1160g
    Tester Dimension
    285mm×85mm×56mm
    Packing:
    Package
    Outer package
    Carton
    Inner package
    Aluminum case
    Accessory
    Meter
    1pcs
    Aluminum Case
    1pcs
    Test Ring
    1pcs
    Manual
    1pcs
    Certification
    1pcs
    Warranty Card
    1pcs